Bb-electronics DELTA Temperature Controller DTB Series Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Bb-electronics DELTA Temperature Controller DTB Series. B&B Electronics DELTA Temperature Controller DTB Series User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 13
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
http://www.delta.com.tw/industrialautomation/
DELTA Temperature Controller
DTB Series
User Manual
Vue de la page 0
1 2 3 4 5 6 ... 12 13

Résumé du contenu

Page 1 - DTB Series

http://www.delta.com.tw/industrialautomation/ DELTA Temperature Controller DTB Series User Manual

Page 2 - User Manual

91030H Start pattern number 0 ~ 7 1040H~ 1047H Actual step number setting inside the correspond pattern 0 ~ 7 = N, indicate that this pattern is ex

Page 3 - 4 Specifications

1014 Panel Cutout and Terminals Identification  Panel Cutout (dimensions are in millimeter and inch)  Terminals Identification DTB4824 65.0 mi

Page 4 - Operation

1115 External Dimensions Dimensions are in millimeter (inch)  DTB4824 

Page 5 - Communication address

1216 Mounting Mounting Method Mounting Bracket InstallationCT Wiring Method (if CT function is selected)Step 1 : Insert the controller through the

Page 6

1B Series Temperature Controller User Manual 1 Precaution DANGER! Caution! Electric Shock! 1. Do not touch the AC terminals while the power is s

Page 7 - 8 Alarm Outputs

24 Specifications 5 Temperature Sensor Type and Temperature Range Input Temperature Sensor Type Register Value LED Display Temperature Ran

Page 8

36 Operation There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operati

Page 9 - 13 RS-485 Communication

4Time setting for valve fromfull close to full open. (Display when valve control is ON)Press Display and adjust output value of 1st output group(Disp

Page 10

57 Dual Loop Output Control (Heating / Cooling Control) OFFPVSet pointONHeatingDead bandHeating hysteresis Figure 1. Output during dual loop outp

Page 11 - 1 432 5 6

68 Alarm Outputs There are up to three groups of alarm outputs and each group allows thirteen alarm types in the initial setting mode. The alarm o

Page 12 - 15 External Dimensions

79 Current Transformer (CT) Function The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) wi

Page 13 - Mounting

813 RS-485 Communication 1. Supporting transmission speed: 2400, 4800, 9600, 19200, 38400bps 2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E

Commentaires sur ces manuels

Pas de commentaire